General Purpose Centrifugal Blower
Operating and Maintenance Manual
I. Application
The general-purpose centrifugal blower is suitable for conveying non-flammable, non-explosive, and non-corrosive gases. The gas temperature shall not exceed 80 °C, and the concentration of dust and hard particulates in the gas shall not exceed 150 mg/m³. It is widely used for general ventilation, air exchange, or localized supply and exhaust in industrial and mining enterprises, warehouses, and other facilities. It can also be used for kitchen exhaust in hotels, inns, cafeterias, and restaurants. Additionally, it can be integrated as a component in specialized equipment such as air purification systems, kitchen equipment, and HVAC units.
II. Installation
1. Before installation, thoroughly inspect the blower for any damage or deformation caused during packing and transportation. If any defects are found, repair them properly before proceeding with installation.
2. During installation, check that all connecting components are secure and free from looseness. The clearance between rotating parts and adjacent components shall be uniform, and there must be no rubbing or collision, such as between the impeller and the inlet or casing, or between the pulley and the belt guard.
3. Regardless of the installation method used, ensure that the installation foundation has sufficient strength and stability. The blower must be securely mounted to prevent safety hazards caused by improper installation.
4. The blower should generally be installed on a suitable concrete foundation and secured with anchor bolts connecting the base feet or base
frame to the foundation. For blowers with smaller sizes and lower motor power, direct flange bolt fixing may also be used.
5. When the blower is suspended from a ceiling (below the floor slab), appropriate hanging rods or hangers shall be used. Note: Large blowers must not be installed by a suspended method.6. It is recommended to connect the blower to the ductwork using a flexible connector. The weight of the ductwork must not be borne by the blower; separate support structures should be provided.
7. Within a distance of two impeller diameters from the blower inlet and outlet, avoid bends or sudden changes in duct cross-section, as these can cause a sharp increase in duct resistance and lead to abnormal blower performance.
8. During electrical installation, the blower must be connected to the correct power supply according to the voltage, frequency, and other information specified on the blower nameplate. Voltage fluctuation shall not exceed ±5% of the rated voltage.
9. Electrical wiring must be performed by qualified professionals and must strictly follow the wiring diagram provided in the terminal box to ensure safety.
10. For blowers with a motor power exceeding 11 kW, it is recommended to equip the system with a reduced-voltage starter (soft starter).
III. Operation and Maintenance
1. Before starting the blower, check for any objects inside the blower or ductwork that may obstruct rotation. Also check for any unsafe conditions near the inlet and outlet (e.g., objects that may be sucked in or blown off). Remove any such objects before starting.
2. A test run must be performed before formal operation to confirm the following:
• A. Correct wiring.
• B. No abnormal noise.
• C. No motor overload.
• D. The rotation direction of the blower matches the direction of airflow.
3. If the rotation direction of the impeller does not match the indicated blower rotation direction, for three-phase power, swap any two of the three phase power leads and retest. For single-phase power, modify the wiring configuration and retest.
4. Most blowers (e.g., 9-19, CF-11, 11-62, DF series, etc.) are strictly prohibited from operating for extended periods with the inlet and outlet open (i.e., without any ducts connected), as this will cause the motor to overload and may burn out the motor. Short-term overload test runs shall not exceed 3 minutes each time.
5. Formal operation shall only commence after the test run has confirmed normal operation.6. Avoid starting and stopping the blower too frequently, as this may easily cause motor burnout.
7. If abnormal noise or increased vibration is observed during blower operation, stop the blower immediately and inspect. The blower may only be returned to service after the fault has been resolved. Abnormal noise and increased vibration are usually caused by a loss of dynamic balance of the impeller, which requires rebalancing.
8. To prevent damage to the blower caused by vibration due to loss of dynamic balance, the impeller shall be inspected at least once a month, and any accumulated dust or oil/grease on the impeller shall be removed promptly.
9. For blowers equipped with a drain hole on the casing, any accumulated liquid (such as oil) inside the blower shall be drained periodically.
10. All blower components shall be inspected periodically to ensure the blower is ready for immediate startup and normal operation.
11. If the blower has been idle for a prolonged period, inspect all connecting components for secure fastening before use, and confirm normal operation through a test run before resuming regular service.
12. While the blower is running, contact with rotating parts such as the impeller, main shaft, belt, and pulley is strictly prohibited to prevent personal injury.
13. Before performing any periodic inspection, repair, or maintenance on the blower, the blower must be stopped and the power supply must be disconnected.
IV. Common faults and cause analysis